FireFlo Design Guide

FireFlo Design Guide

Designing your heat collector system

Features

The standard FireFlo panel dimensions are 2870mm x 320mm x 50mm without the end connections. The mounting arrangement selected will affect the end connection configuration and hence the overall dimensions.

The standard pipework connection is a DN32 PN16 raised face flange. This allows for a connection with reliable sealing and easy connection to polyethylene pipework.
As standard, 3 collector panels should be mounted in series. This can be adjusted for a specific application if required.

The flat panel design of the FireFlo collectors allows them to be easily cleaned and reduces the likelihood of debris from the watercourse becoming caught up on the plates.
There are individual bleed points on each of the panels to allow any entrained air to be bled during filling and after the initial running of the system.

Single FireFlo Collector Panel

Single FireFlo Collector Panel

The budget price for a single FireFlo collector panel is £1,950 excluding VAT. Contact the FireFlo team for a quotation.

^Index

 

FireFlo technical data

Mass and Dimensions

FireFlo Mass and Dimensions
Assembly

Approx. Mass / Volume

Empty Mass

Filled Mass

Filled Volume

Overall dimensions (l x w x h)
Single panel assembly 35 kg
75 kg
40 l
3086 mm x 406 mm x 140 mm
3 panel assembly 98 kg
218 kg
120 l
3080 mm x 332 mm x 390 mm

Single panel assembly dimensions

Single panel assembly dimensions

3 panel assembly dimensions

3 panel assembly dimensions

FireFlo connection sizes
Flow and return connections DN32 PN16 raised face flanges
Bleed point connection ¼” BSP

^Index

Materials

FireFlo materials
Side plates, dividers and brackets Stainless-steel 304 2B1
Bleed point connection Stainless-steel 304 and 3161
Bleed plug seal EPDM
1 All stainless-steel 316 upgrade available.  

^Index

Operating Data

FireFlo operating data
Recommended operating pressure 1.8 bar
Maximum operating pressure 2.0 bar
Burst pressure 2.5 bar
Recommended brine flow rate 0.9 l/s (can be adjusted to match heat pump specification)
Minimum brine flow rate 0.5 l/s
Pressure loss at recommended brine flow 4.6 kPa (3 panel assembly)
Minimum operating temperature -10°C
Maximum operating temperature 50°C

^Index

FireFlo Precision Manufacturing

FireFlo Precision Manufacturing

Pressure Loss

The curve below shows the pressure loss through a 3-panel assembly at varying brine flow rates. This is based on a brine solution consisting of water with 20% ethylene glycol at 0°C.

A single panel assembly will have approximately 1/3 of the pressure loss.

FireFlo pressure loss

FireFlo pressure loss

The recommended flow rate through the FireFlo panels is 0.9 l/s. Greater brine flowrates result in improved heat transfer but higher pressure loss. The benefit of increasing the brine flowrate reduce the more it is increased. It is recommended to operate the panels with a brine flowrate greater than 0.5 l/s to avoid a significant drop in the rate of heat transfer.

^Index

Heat transfer characteristics

The thermal energy collected by the FireFlo panels is dependent on a number of variables:

  • Water velocity in the channel.
  • Brine flowrate through the panels.
  • Properties of the brine solution.
  • Installation conditions.

The following graphs provide the expected FireFlo thermal output at a range of river velocities for the following conditions2:

  • Recommended brine solution flowrate of 0.9 litres per second through each panel.
  • 20% ethylene glycol brine solution (suitable for a minimum working temperature of -10°C).

2 Note: the brine flow and return temperatures stated in the graphs below have been used to calculate the mean temperature difference between the brine and the watercourse. This does not necessarily reflect the brine flow and return temperatures for a single collector assembly.

The curves shown are for different channel velocities and brine flow and return temperatures.
To obtain an approximate sizing for a UK application, the curve for a river temperature of 5°C and brine flow and return temperatures of -4°C and 0°C respectively should be used. 5°C is a typical minimum UK freshwater temperature, but this will vary between sites.

The data below is relevant for a wall mounted 3 panel assembly (output is given per panel, so multiply by 3 for the 3 panel assembly). This data can also be used for estimating the performance of the vertical and horizontal bed mounted arrangements (refer to General for standard mounting arrangements):

FireFlo thermal output when wall mounted (5°C river temp. -4 to 0°C brine temp. is used for a typical UK sizing).

FireFlo thermal output when wall mounted (5°C river temp. -4 to 0°C brine temp. is used for a typical UK sizing).

The data below is relevant for a partially embedded single panel assembly:

FireFlo Embedded Panel Thermal Output graph

FireFlo Embedded Panel Thermal Output graph

Contact the FireFlo team for assistance with design for a specific site.

^Index

Standard installation configurations

General

There are 4 standard mounting configurations that allow the FireFlo system to be adapted to a range of channel conditions.

For some mounting arrangements, the panels are provided as a 3-panel fabrication as standard. For other mounting arrangements, the interconnections between panels will be made up on site by the installer.

Standard mounting arrangement summary
Mounting arrangement Standard module Minimum watercourse depth for full utilisation
Wall mounted 3-panel arrangement 450 mm for a single module, with an additional 420 mm for each additional stacked module
Bed mounted, horizontal panels 3-panel arrangement 450 mm
Bed mounted, horizontal panels Single panels 250 mm
Bed mounted, embedded panels Single panels >50 mm

The brackets required for each mounting arrangement can be supplied as a standard kit. Additional brackets can be supplied to assist with supporting connecting pipework.

The flow and return arrangement for the FireFlo assemblies will generally utilise 40mm PE pipe.

^Index

 Wall mounted arrangement

The wall-mounted panel arrangement uses a standard bank of 3 FireFlo panels which are supplied as a single fabricated assembly. These can then be fixed to wall mounting brackets and stacked in multiple layers if required and if the depth of water permits this.

If the mounting assembly is specified with an order, the correct brackets and fixings for the number of panel layers will be provided.

During installation, generally the wall brackets will be fixed in place initially. The FireFlo assemblies will then be mounted onto the cantilever brackets and bolted down. Each assembly of 3 FireFlo panels can be installed and removed independently of the other layers.

The flow and return connections for each FireFlo assembly are at opposite ends of the panels.

Wall mounted FireFlo installation

Wall mounted FireFlo installation

^Index

 

Bed mounted, vertical panel arrangement

The bed-mounted arrangement with vertically orientated panels uses the same standard bank of 3 FireFlo panels as the wall mounted arrangement.

The standard bracket arrangement allows the panels to be mounted to the base of a channel. The standard levelling brackets allow for direct mounting to a solid surface. Optional mounting plates can be supplied to allow for mounting to a soft bed. These can either be fixed down to the bedrock below or held down with earth anchors.

If the mounting assembly is specified with an order, the correct brackets and fixings for the number of FireFlo assemblies will be provided.

During installation, the brackets will be fixed in place initially. The FireFlo assemblies will then be mounted to the channel section supports.

The flow and return connections for each FireFlo assembly are at opposite ends of the panels.

Bed mounted vertically orientated FireFlo installation

Bed mounted vertically orientated FireFlo installation

^Index

 

Bed mounted, horizontal panel arrangement

The bed-mounted arrangement with horizontally orientated panels uses single FireFlo panel assemblies. These can be connected in series with each other.

The standard bracket arrangement is the same as for the bed mounted arrangement with vertically orientated panels.
The flow and return connections for each FireFlo assembly are at opposite corners of the panel. The flange faces are parallel with the long edge of each panel.

The simplest mounting arrangement is 3 single panel assemblies connected in series and mounted side by side. However, the assemblies can also be installed inline if the channel is narrow. Additional interconnecting pipework is required for inline installation.

Panels are supplied with brackets mounted on side A or side B to enable simple interconnections.

Bed mounted horizontally orientated FireFlo installation

Bed mounted horizontally orientated FireFlo installation

^Index

 

Bed mounted, embedded panel arrangement

The bed-mounted arrangement with embedded panels uses single FireFlo panel assemblies. These can be connected in series with each other.

This mounting arrangement results in only one face in contact with the flowing water so is only recommended for shallow channels. Embedding the panels means that the additional obstruction in the watercourse is minimal.

Hold down brackets are fixed directly to either end of the panels for anchoring.

The simplest mounting arrangement is 3 single panel assemblies connected in series and assembled side by side. However, the assemblies can also be installed inline if the channel is narrow. Additional interconnecting pipework is required for inline installation.

Panels are supplied with brackets mounted on side A or side B to enable simple interconnections).

Bed mounted, embedded FireFlo installation

Bed mounted, embedded FireFlo installation

^Index

 

Array mounting for static water applications

FireFlo heat collectors are designed for flowing-water applications, but they can also be used in static water (ponds, lakes, canals etc.) provided that enough collectors are installed to compensate for the reduced amount of heat collection that is possible from static water because of the reduced heat transfer.

To facilitate installation the FireFlo collectors can be supplied with upper and lower brackets of the correct length to fasten the collector sub-assemblies together and also provide convenient attachment points for top-hung mounting arrangements or ballasting arrangements underneath the FireFlo collectors. Note that the large number of mounting holes provided on the bracket flanges are to give you multiple connection point options – just use an appropriate number of connections points in the positions that suite your application.
If using ballast weights underneath the collector array, it is best to use just enough ballast to hold the array on the bed in normal use, but still allows the array to float back up to the surface if the internal brine is displaced by compressed air, which makes it much easier to access the collectors for maintenance. When ballasted onto the bed, some type of spacer is normally added underneath the collector array so that it doesn’t sit right onto the bed where it can be susceptible to silt accumulation. Suitable spacers can be hollow concrete blocks that are also used as ballast, or old plastic bread or bottle crates. A standoff of approx. 250 mm is recommended.

Note that the image below shows an example of a 9-collector array, with flow and return connections for each sub-assembly of three FireFlo collectors. Array connections can be configured in any arrangement to meet the specifics of your system flow and return parameters.

Array mounting for static water Fireflo installation

Array mounting for static water Fireflo installation

^Index

Collector system design

 

Typical system layout

The following image shows a typical collector system layout with the fill/purge system connected. Generally, this would only be connected during the initial filling process.

Typical collector system configuration incorporating FireFlo collectors

Typical collector system configuration incorporating FireFlo collectors

^Index

 

Connecting multiple FireFlo assemblies

Multiple FireFlo assemblies can be connected in series or in parallel. Series connection results in a greater flow through each collector. This provides a benefit in terms of heat transfer. However, it will also result in increased pressure loss. The decision to connect FireFlo assemblies in series or parallel is therefore mainly driven by the specification of the brine circulation pump.

Where FireFlo assemblies are connected in parallel, flow and return manifolds are required to supply each of the collector loops. If the collector loops do not have equal flow resistance, a commissioning valve will need to be incorporated into each collector loop. This will enable the flow through each loop to be balanced during commissioning.

Reverse return connection is one way of ensuring each parallel loop has the same flow resistance.

Contact the FireFlo team to discuss your manifold requirements.

Reverse return configuration

Reverse return configuration

^Index

 

Overpressure protection

The Fireflo system must be protected from being over pressurised to prevent damage to the panels using a safety relief valve or rupture disc. This over pressure device must be located on the flow pipe between the brine pump and the first FireFlo panel. It should discharge to a foul water drain.

The overpressure device should be designed to discharge all available brine pump flow to the drain when the FireFlo panels are at their maximum operating pressure. When sizing the over pressure device, it is important to consider the difference in elevation between the overpressure device and the lowest point of the FireFlo panels. An example of sizing the overpressure device is given below.

Example:

  • Maximum allowable FireFlo operating pressure = 2.0 bar.
  • Position of over pressure device above lowest point in FireFlo system = 3m (0.3 bar).
  • Overpressure device maximum pressure at design discharge = 2.0 – 0.3 = 1.7 bar (pressure at which the design flowrate is discharged through the device).
  • Brine pressure at location of overpressure device when brine pump is off = 0.5 bar.
  • Pressure across brine pump during normal operation = 0.2 bar.
  • Maximum brine pressure at location of overpressure device = 0.5 + 0.2/2 = 0.6 bar.
  • Overpressure device minimum pressure at zero discharge flow = 0.6 bar (to prevent false trips).
  • Selected overpressure device type = NABIC Fig 542 Safety Relief Valve.
  • Selected overpressure device set pressure = 1.0 bar.
  • Selected overpressure device pressure at design discharge flowrate = 1.1 bar (10% overpressure).
  • Brine pump minimum differential pressure during overpressure event = 1.1 – 0.5 = 0.6 bar.
  • Brine pump flowrate at minimum differential pressure = 60 kg/min.
  • Overpressure device minimum size required = DN20

NABIC Safety Relief Valves are suggested valves for overpressure protection and should be sized for the application.

If in doubt, contact the FireFlo team who will be able to quote a suitable overpressure device.

^Index

 

Expansion vessels

The FireFlo system should contain an expansion vessel to absorb pressure surges and fluctuations with temperature.

An approximate size for the expansion vessel is 5% of the brine circuit capacity. However, this should be discussed with the heat pump supplier.

The gas in the expansion vessel should be charged to the design pressure in the system at the location of the expansion vessel.

If in doubt, contact the FireFlo team who will be able to quote a suitable expansion vessel.

^Index

 

Provision for filling

Connection points for filling the collector system with brine solution should be incorporated as per the heat pump manufacturer’s instructions.

The filling pump system must incorporate a pressure relief valve to prevent the FireFlo panels being over pressurised by the filling pump. The pressure relief valve connected to the filling pump must be set sufficiently low such that the maximum operating pressure of the FireFlo panels is not exceeded.

Air bleed points must also be incorporated at any high points in the system. The use of automatic deaerators at high points is also recommended (above water level only).

Incorporating a manual fill connection supplied by mains water is also recommended. This connection must follow WRAS regulations and be disconnected when not in use. The manual fill loop should be connected to the cold-water supply via a double check valve. The manual fill connection will ease the process of topping up the system when air is bled following the initial filling process.

The manual fill connection should be fed via a pressure reducing valve. The pressure reducing valve setpoint should be set to a pressure above the desired brine loop pressure, but sufficiently low to prevent the FireFlo panels being over pressurised. This manual fill loop should also contain a shutoff valve and should be disconnected after filling so that the system is isolated from the water supply.

The overpressure device must remain connected during the initial filling process and whilst using the manual fill connection.

^Index

Pipework Guide

Introduction

This guide explains the how the FireFlo collectors are connected to the heat pump and the type of pipe and connections used.
It is important that these guidelines are followed to ensure that the pipework and connections seal completely and will have long-term durability. The methods and parts specified have been carefully selected to ensure compatibility both from a mechanical perspective and chemical compatibility between the recommend heat transfer fluid (Kilfrost Geo) and the various polymer materials

^Index

Heat transfer fluid

There are a number of heat transfer fluids that can be used in the collector loops of water-source heat pumps, but some are better than others. The main options are:

  • Kilfrost Geo
  • Monoethylene Glycol (such as Thermox DTX)
  • Polypropylene Glycol

Kilfrost Geo
Kilfrost Geo is the recommended heat transfer fluid for use with FireFlo collectors. It is significantly more environmentally-friendly than the other options, has a lower viscosity in the normal operating temperature range (which means lower head losses and lower pumping costs), has the best heat-transfer characteristics while still containing the corrosion inhibitors found in most good quality heat transfer fluids. It is a similar price to the alternatives, so considering the technical and environmental advantages it offers it is a win/win choice.

Note that a food-grade version is also available if needed – Kilfrost Geo Plus.

Monoethylene Glycol (such as Thermox DTX)
Monoethylene Glycol heat transfer fluids are also suitable for use with FireFlo collectors and are compatible with PVC pipework components (if used), but note that it is more viscous than Kilfrost Geo (hence the pressure drop and pumping cost will be greater), is not as good from a heat-transfer perspective and is significantly more damaging to the aquatic environment if it leaks out due to its higher BOD (Biological Oxygen Demand) and COD (Chemical Oxygen Demand) – even if the fluid contains detoxifying additives to make it more biodegradable. Monoethylene Glycol is very toxic to mammals, so needs additional care when handling by human operatives because it is dangerous to inhale or get on your skin, amongst other things, so better to avoid and use Kilfrost Geo instead.

Polypropylene Glycol
Polypropylene Glycol is very viscous so is a poor choice for water-source heat pump projects, and has a poorer heat transfer performance. It is also not compatible with PVC polymers, so cannot be used if there are any PVC materials in the pipework. Therefore, Polypropylene Glycol is not recommended for use with FireFlo collectors – use Kilfrost Geo instead.

^Index

Pipes

The pipe used between the FireFlo collectors and the manifold (if used) or heat pump is normally made from either Flexible PVC, HDPE or stainless steel. For most applications Flexible PVC is the most practical option, though the others will work well if preferred. If HDPE or stainless-steel pipes are used, DN32 PN16 flanges will need to be fitted to the FireFlo collectors, as described below under ‘Connections to FireFlo collectors’.
Flexible PVC pipe
Flexible PVC pipe has a number of practical advantages:

  • All bends are long-radius, which lowers head losses / pumping losses.
  • Routing the pipe between the collector(s) and manifold is easier because the pipe can follow any route, and doesn’t need numerous elbows to be fitted.
  • It is easier to make connections with the added flexibility to align connections.
  • The length of the pipework does not have to be exactly right to make-up connections, as is the case with rigid MDPE and stainless-steel pipework.
  • It is much quicker to install when working in a wet environment.

There are some disadvantages to consider:

  • Flexible PVC pipe should not be buried direct into the ground, unless it is inside a rigid duct to avoid the risk of crushing.
  • Flexible PV pipe cannot be routed over sharp-edged objects (like over the top of a wall) because it will kink, significantly increasing head losses and probably get punctured over time.
  • If there is any risk of vandalism (puncturing the pipe etc.), rigid pipe would be better.

Provided the disadvantages above are considered and mitigated against, FireFlo recommends flexible PVC pipework because of the numerous practical advantages it provides.

For Flexible PVC pipe, FireFlo recommends 1 ¼” / 32 mm ID Merlett Vacupress Superelastic pipe.

^Index

Connections to FireFlo collectors

FireFlo collectors have an integral 304 stainless steel 1 ¼” BSPT (final T meaning ‘tapered’) male threaded connection for the pipework connections. This will connect to any 1 ¼” BSPP (Final P meaning ‘parallel’) or BSPT threaded female connection, with a thread sealant applied to the threads.

FireFlo recommends Loctite 567 as a thread sealant, and Loctite SF 7070 solvent cleaner for cleaning the threads prior to applying the thread sealant.

Flexible PVC pipework

Assuming the recommended Flexible PVC pipe is used, we recommend screwing a 1 ¼” BSPT female stainless-steel hose tail fitting for 1 ¼” ID pipe (32 mm) into the FireFlo collector connection (using a thread sealant) which would then join onto the recommended flexible PVC hose discussed above using either an Oetiker ‘Ear Clamp’ (preferred) or durable screw-type hose clip (i.e. Mikalor W4)

FireFlo can supply the hose tails pre-assembled onto the PVC flexible pipe to your specified length, using an Oetiker ‘ear clamp’ to join the pipe to the hose tail, which are extremely strong and long-lasting. FireFlo can also supply all of the stainless-steel fittings if required. The recommended arrangement is shown in the figure below.

FireFlo collector connected to Flexible PV hose.

FireFlo collector connected to Flexible PV hose.

The assembly shown in Figure 1 would need to be screwed into the FireFlo collector, which means that the other end of the same pipe must be disconnected to allow it to rotate while being screwed in. How the other end of the pipes that connect to the manifold or heat pump are configured will be left to the installer to determine because they will know best.

If you prefer to connect your pipework to the FireFlo collectors using rigid pipework (HDPE or stainless steel), the connections to FireFlo collectors will have to be with a DN32 PN16 flange (note PN10 and PN16 are identical at this size) with a 1 ¼” BSPT or BSPP female thread. This can be achieved stainless steel fittings as shown below. As before, a pipe sealant be should be used between all threaded connections.

Note that in all cases, for 1 ¼” BSPT/BSPP fittings with thread sealant applied, they should be tightened to ½ to 1 ½ turns beyond finger tight. Basically, aim for the minimum, then if needed turn further to align the fitting as required.

^Index

Connection to FireFlo collector using DN32 PN16 flanged connection.

Connection to FireFlo collector using DN32 PN16 flanged connection.

^Index

Pipe retention

All pipework should be appropriately supported and anchored. The best way of doing this is often determined by the installer because it can be very site-specific in design.

Note that in wall-mounted applications of multiple FireFlo collectors, the welded-on spacers shown in the figure below have a 9 mm hole / M8 hole which can be used to attach a pipe support of other bracketry. If you require bespoke fabricated bracketry, FireFlo may be able to provide this for an additional fee.

Attachment points for pipe supports, if needed. Attachment points for pipe supports, if needed.

If flexible pipes need holding down onto the bed, sand / gravel / clay-filled sandbags are good for this. Normally one bag per metre of pipe length is adequate.

^Index

 

Design considerations when designing pipework

  • With flexible pipe, avoid sharp edges.
  • If vandals / tampering with pipework is likely, avoid flexible pipework where accessible out-of-water.
  • With multiple-strings of parallel FireFlo collectors a manifold may be needed to connect the strings to the primary pipework. This manifold may also include flow balancing valves and filling / draining connections. Manifold design will be undertaken by the installer.

Are you considering a FireFlo heat collector ?

FireFlo heat collectors are now installed and operating in rivers in the UK, as an essential component to Water Source Heat Pump installations. FireFlo heat collectors are designed and manufactured in Britain. Our FireFlo collectors are available in the United Kingdom and the European Union or other countries by agreement. Your first step is to check our Design Guide , Sizing and Pricing Guide and our Installation Guide. Interested? Please Get in touch

If you would like more information or a quote please us the Enquiry page or call us on +44 (0)1453 88 77 44.